Electric circuits and connections in homes
In a home network devices are connected in parallel, so each gets 220 V and switching one off does not affect the others. The network has two wires: a phase wire (with dangerous voltage) and a neutral wire; both must be treated as dangerous. If the circuit is overloaded or shorted, the current grows and wires can heat up and start a fire; to prevent this a fuse is installed: when the current exceeds the allowed value, the thin wire inside it melts and breaks the circuit. Industry often uses a three-phase 380 V network. Connecting, replacing or repairing a plug, socket or lamp holder is done only by adults or an electrician; children must not put anything into a socket or touch electrical devices with wet hands.
A tailoring workshop’s line has a 25 A breaker, so the largest power is 25 · 220 = 5500 W. Three lamps (100 W each) and four sewing machines (300 W each) draw 300 + 1200 = 1500 W together, far below the limit, so the breaker stays on.
Electricians choose a breaker and cable for each line, building inspectors check the safety of wiring, and maintenance staff watch that the load does not grow too large.
On paper, list three high-power appliances (for example a kettle, an iron, a heater) and explain why they should not share one extension lead: their powers add up.
With an adult look at where the electric supply enters your home and where the fuse (breaker) is (just look, do not touch) and draw a simple diagram.